(a) Cathodic protection shall be installed and operated on all internally lined underground storage tanks no later than June 30, 2008.
(b) All underground storage tank systems that dispense more than five hundred thousand (500,000) gallons per month of a regulated substance shall be replaced with double wall tanks and lines with interstitial leak monitoring no later than June 30, 2012, or thirty (30) years from the date of installation of the underground storage tank, whichever is later.
(c) Double wall underground storage tanks and lines with interstitial leak monitoring shall be installed whenever any underground storage tank is installed.
(d) Double wall underground storage tank system lines with interstitial leak monitoring shall be installed whenever any line is installed on any underground storage tank system. Except piping connected to field-constructed underground storage tank systems with a capacity exceeding fifty thousand (50,000) gallons or piping that is used for an airport hydrant system, if existing single wall underground piping connected to an underground storage tank system fails due to corrosion or fails and has been recalled by the manufacturer, the entire run of single wall piping shall be replaced with double wall piping with interstitial monitoring regardless of the length of piping requiring repair.
(e) The council may promulgate rules and regulations to administer this section after recommendation from the director.
(f) A double wall and interstitially monitored underground storage tank or underground piping installed after December 1, 2005, shall be interstitially monitored for the lifetime of the tank or piping.
(g) Except essential homeland security systems, emergency generator systems and systems used for other disaster relief efforts, if a new piping interstitial monitoring system is installed and sump sensors are used as standalone automatic leak detectors, the system shall be configured to shut off the flow of product in that piping run when a sump sensor triggers an alarm.
Cite this article: FindLaw.com - Wyoming Statutes Title 35. Public Health and Safety § 35-11-1429. Tank requirements; rulemaking authority - last updated January 01, 2024 | https://codes.findlaw.com/wy/title-35-public-health-and-safety/wy-st-sect-35-11-1429/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)