Texas Property Code - PROP § 92.257. Installation Procedure

Welcome to FindLaw's Cases & Codes, a free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw's Learn About the Law.

(a) Subject to Subsections (b) and (c), a smoke alarm must be installed according to the manufacturer's recommended procedures.

(b) A smoke alarm must be installed on a ceiling or wall.  If on a ceiling, it must be no closer than six inches to a wall or otherwise located in accordance with the manufacturer's installation instructions.  If on a wall, it must be no closer than six inches and no farther than 12 inches from the ceiling or otherwise located in accordance with the manufacturer's installation instructions.

(c) A smoke alarm may be located other than as required by Subsection (a) or (b) if a local ordinance or a local or state fire marshal approves.