(a) Fuses and automatic circuit breakers shall be so constructed as to effectively interrupt the current on short circuit, or when the current through them exceeds a predetermined value. Open type fuses shall be provided with terminals. Circuit breakers shall be of adequate interrupting capacity, adjustable to trip at from fifty percent to one hundred fifty percent of their normal rated capacity.
(b) Circuit breakers used to protect feeder circuits shall be set to trip when the current exceeds by more than fifty percent the current carrying capacity of the feeder. In case the feeder is subjected to overloads, sufficient to trip the circuit breaker, but of short duration, the circuit breaker may be equipped with a device which will prevent its acting unless the overload persists for a longer period than ten seconds. Trip current shall be indicated at the circuit breaker.
(c) Fuses shall be stamped or marked, or shall have a label attached indicating the maximum current which they are intended to carry. Fuses shall only be adjusted or replaced by a competent person authorized by the mine foreman. Wire or other conducting materials shall not be used as a substitute for properly designed fuses.
(d) Fuses used to protect feeders shall not be greater than the current rating of the feeder.
(e) All switches, circuit breakers and fuses shall have incombustible bases.
(f) Operating controls, such as starters, switches and switch buttons, shall be so installed that they are readily accessible and can be operated without danger of contact with moving or live parts. On stationary equipment provision shall be made for locking starting equipment in “off” position to prevent accidental application of power.
(g) Circuit breakers and disconnect switches shall be installed underground in all main power circuits within five hundred feet of the bottom of shafts, boreholes and inclines, where main power circuits enter the mine.
Cite this article: FindLaw.com - Pennsylvania Statutes Title 52 P.S. Mines and Mining § 70-1113. Switches, fuses and circuit breakers - last updated January 01, 2025 | https://codes.findlaw.com/pa/title-52-ps-mines-and-mining/pa-st-sect-52-70-1113/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)