(a) Except for unattended field compressor stations of 1,000 horsepower (746 kilowatts) or less, each compressor station must have an emergency shutdown system that meets the following:
(1) It must be able to block gas out of the station and blow down the station piping.
(2) It must discharge gas from the blowdown piping at a location where the gas will not create a hazard.
(3) It must provide means for the shutdown of gas compressing equipment, gas fires, and electrical facilities in the vicinity of gas headers and in the compressor building, except that:
(i) Electrical circuits that supply emergency lighting required to assist station personnel in evacuating the compressor building and the area in the vicinity of the gas headers must remain energized; and
(ii) Electrical circuits needed to protect equipment from damage may remain energized.
(4) It must be operable from at least two locations, each of which is:
(i) Outside the gas area of the station;
(ii) Near the exit gates, if the station is fenced, or near emergency exits, if not fenced; and
(iii) Not more than 500 feet (153 meters) from the limits of the station.
(b) If a compressor station supplies gas directly to a distribution system with no other adequate source of gas available, the emergency shutdown system must be designed so that it will not function at the wrong time and cause an unintended outage on the distribution system.
(c) On a platform located offshore or in inland navigable waters, the emergency shutdown system must be designed and installed to actuate automatically by each of the following events:
(1) In the case of an unattended compressor station:
(i) When the gas pressure equals the maximum allowable operating pressure plus 15 percent; or
(ii) When an uncontrolled fire occurs on the platform; and
(2) In the case of a compressor station in a building:
(i) When an uncontrolled fire occurs in the building; or
(ii) When the concentration of gas in air reaches 50 percent or more of the lower explosive limit in a building which has a source of ignition.
For the purpose of paragraph (c)(2)(ii) of this section, an electrical facility which conforms to Class 1, Group D, of the National Electrical Code is not a source of ignition.
Cite this article: FindLaw.com - Code of Federal Regulations Title 49. Transportation § 49.192.167 Compressor stations: Emergency shutdown - last updated October 02, 2022 | https://codes.findlaw.com/cfr/title-49-transportation/cfr-sect-49-192-167/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature or via Westlaw before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw's Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)