(a) The total emergency venting capacity (Q) of the relief devices of an uninsulated MPT must be in accordance with Table 1 or the following formula based upon the pressure relief device operating at a pressure not to exceed the test pressure:
|
Q= |
633,000 |
(A0.82/LC) |
square root(ZT/M) |
where:
Q=Minimum required rate of discharge in cubic feet per minute of free air at standard conditions (60° F and 14.7 psia).
M=Molecular weight of the product, or 86.7.
T=Temperature, degrees Rankine (460° + temperature in degrees F of gas at relieving temperature), or 710° Rankine.
A=Total external surface area of the tank compartment in square feet.
L=Latent heat of the product being vaporized at relieving conditions in Btu per pound, or 144 Btu per pound.
Z=Compressibility factor of the gas at relieving conditions, or 1.0.
C=Constant based on relation of specific heats, in accordance with appendix J of division 1 of section VIII of the ASME Code, 1974 edition, or 315.
(b) The total emergency venting capacity (Q) of an insulated portable tank may have a reduction if—
(1) It is shown to the Coast Guard that the insulation reduces the heat transmission to the tank;
(2) The present reduction of the emergency venting capacity (Q) is limited to the percent reduction of the heat transmission to the tank or 50 percent, whichever is less; and
(3) The insulation is sheathed.
|
TABLE 1—Minimum emergency venting capacity in cubic feet: free air/hour (14.7 lb/in2a and 60° F) |
|||
|---|---|---|---|
|
Exposed area square feet1 |
Cubic feet free air per hour |
Exposed area square feet1 |
Cubic feet free air per hour |
|
20 |
27,600 |
275 |
237,000 |
|
30 |
38,500 |
300 |
256,000 |
|
40 |
48,600 |
350 |
289,500 |
|
50 |
58,600 |
400 |
322,100 |
|
60 |
67,700 |
450 |
355,900 |
|
70 |
77,000 |
500 |
391,000 |
|
80 |
85,500 |
550 |
417,500 |
|
90 |
94,800 |
600 |
450,000 |
|
100 |
104,000 |
650 |
479,000 |
|
120 |
121,000 |
700 |
512,000 |
|
140 |
136,200 |
750 |
540,000 |
|
160 |
152,100 |
800 |
569,000 |
|
180 |
168,200 |
850 |
597,000 |
|
200 |
184,000 |
900 |
621,000 |
|
225 |
199,000 |
950 |
656,000 |
|
250 |
219,500 |
1,000 |
685,000 |
1 Interpolate for intermediate sizes.
Cite this article: FindLaw.com - Code of Federal Regulations Title 46. Shipping § 46.64.63 Minimum emergency venting capacity - last updated January 02, 2025 | https://codes.findlaw.com/cfr/title-46-shipping/cfr-sect-46-64-63/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)