(a) A dual voltage generator installed on a vessel shall be of the grounded type, where:
(1) The neutral of a dual voltage system must be solidly connected at the switchboard's neutral bus; and
(2) The neutral bus shall be connected to ground.
(b) The neutral of a dual voltage system must be accessible for checking the insulation resistance of the generator to ground before the generator is connected to the bus.
(c) Ground detection must be provided that:
(1) For an alternating current system, meets § 111.05–27 in subchapter J of this chapter; and
(2) For a direct current system, meets § 111.05–29 in subchapter J of this chapter.
Cite this article: FindLaw.com - Code of Federal Regulations Title 46. Shipping § 46.183.324 Dual voltage generators - last updated January 02, 2025 | https://codes.findlaw.com/cfr/title-46-shipping/cfr-sect-46-183-324/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)