(a) Any existing point subject to this subpart must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT):
|
BCT effluent limitations |
||
|---|---|---|
|
Pollutant or pollutant property |
Maximum for any 1 day |
Average of daily values for 30 consecutive days shall not exceed |
|
Metric units (kilograms per 1,000 m3 of feedstock) |
||
|
BOD5 |
54.4 |
28.9 |
|
TSS |
37.3 |
23.7 |
|
Oil and grease |
17.1 |
9.1 |
|
pH |
(1) |
(1) |
|
English units (pounds per 1,000 bbl of feedstock) |
||
|
BOD5 |
19.2 |
10.2 |
|
TSS |
13.2 |
8.4 |
|
Oil and grease |
6.0 |
3.2 |
|
pH |
(1) |
(1) |
1 Within the range of 6.0 to 9.0.
(b) The limits set forth in paragraph (a) of this section are to be multiplied by the following factors to calculate the maximum for any one day and maximum average of daily values for thirty consecutive days.
(1) Size factor.
|
1,000 bbl of feedstock per stream day |
Size factor |
|---|---|
|
Less than 124.9 |
0.73 |
|
125.0 to 149.9 |
0.76 |
|
150.0 to 174.9 |
0.83 |
|
175.0 to 199.9 |
0.91 |
|
200.0 to 224.9 |
0.99 |
|
225.0 or greater |
1.04 |
(2) Process factor.
|
Process configuration |
Process factor |
|---|---|
|
Less than 6.49 |
0.75 |
|
6.5 to 7.49 |
0.82 |
|
7.5 to 7.99 |
0.92 |
|
8.0 to 8.49 |
1.00 |
|
8.5 to 8.99 |
1.10 |
|
9.0 to 9.49 |
1.20 |
|
9.5 to 9.99 |
1.30 |
|
10.0 to 10.49 |
1.42 |
|
10.5 to 10.99 |
1.54 |
|
11.0 to 11.49 |
1.68 |
|
11.5 to 11.99 |
1.83 |
|
12.0 to 12.49 |
1.99 |
|
12.5 to 12.99 |
2.17 |
|
13.0 or greater |
2.26 |
(3) See the comprehensive example in subpart D, § 419.42(b)(3).
(c) The provisions of § 419.14(c) apply to discharges of process wastewater pollutants attributable to ballast water by a point source subject to the provisions of this subpart.
(d) The quantity and quality of pollutants or pollutant properties controlled by this paragraph, attributable to once-through cooling water, are excluded from the discharge allowed by paragraph (b) of this section.
(e) Effluent limitations for contaminated runoff. The following effluent limitations constitute the quantity and quality of pollutants or pollutant properties controlled by this paragraph and attributable to contaminated runoff which may be discharged after the application of the best conventional pollutant control technology by a point source subject to this subpart.
(1) If wastewater consists solely of contaminated runoff and is not commingled or treated with process wastewater, it may be discharged if it does not exceed 15 mg/l oil and grease based upon an analysis of any single grab or composite sample.
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by the permit writer times the concentrations listed in the following table:
|
BCT effluent limitations for contaminated runoff |
||
|---|---|---|
|
Pollutant or pollutant property |
Maximum for any 1 day |
Average of daily values for 30 consecutive days shall not exceed |
|
Metric units (kilograms per 1,000 m3 of feedstock) |
||
|
BOD5 |
48. |
26. |
|
TSS |
33. |
21. |
|
Oil and grease |
15. |
8. |
|
pH |
(1) |
(1) |
|
English units (pounds per 1,000 gallons of flow) |
||
|
BOD5 |
0.40 |
0.22 |
|
TSS |
0.28 |
0.18 |
|
Oil and grease |
0.13 |
0.067 |
|
pH |
(1) |
(1) |
1 Within the range of 6.0 to 9.0.
Cite this article: FindLaw.com - Code of Federal Regulations Title 40. Protection of Environment § 40.419.54 Effluent limitations guidelines representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT) - last updated January 02, 2025 | https://codes.findlaw.com/cfr/title-40-protection-of-environment/cfr-sect-40-419-54/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)