(a) Monitoring.
(1) If you submitted an IDSE report, you must begin monitoring at the locations and months you have recommended in your IDSE report submitted under § 141.605 following the schedule in § 141.620(c), unless the State requires other locations or additional locations after its review. If you submitted a 40/30 certification under § 141.603 or you qualified for a very small system waiver under § 141.604 or you are a nontransient noncommunity water system serving <10,000, you must monitor at the location(s) and dates identified in your monitoring plan in § 141.132(f), updated as required by § 141.622.
(2) You must monitor at no fewer than the number of locations identified in this paragraph (a)(2).
Source water type |
Population size category |
Monitoring Frequency 1 |
Distribution system monitoring location total per monitoring period 2 |
---|---|---|---|
Subpart H: |
|||
<500 |
per year |
2 |
|
500-3,300 |
per quarter |
2 |
|
3,301-9,999 |
per quarter |
2 |
|
10,000-49,999 |
per quarter |
4 |
|
50,000-249,999 |
per quarter |
8 |
|
250,000-999,999 |
per quarter |
12 |
|
1,000,000-4,999,999 |
per quarter |
16 |
|
≥ 5,000,000 |
per quarter |
20 |
|
Ground Water: |
|||
<500 |
per year |
2 |
|
500-9,999 |
per year |
2 |
|
10,000-99,999 |
per quarter |
4 |
|
100,000-499,999 |
per quarter |
6 |
|
≥ 500,000 |
per quarter |
8 |
1 All systems must monitor during month of highest DBP concentrations.
2 Systems on quarterly monitoring must take dual sample sets every 90 days at each monitoring location, except for subpart H systems serving 500–3,300. Ground water systems serving 500–9,999 on annual monitoring must take dual sample sets at each monitoring location. All other systems on annual monitoring and subpart H systems serving 500–3,300 are required to take individual TTHM and HAA5 samples (instead of a dual sample set) at the locations with the highest TTHM and HAA5 concentrations, respectively. For systems serving fewer than 500 people, only one location with a dual sample set per monitoring period is needed if the highest TTHM and HAA5 concentrations occur at the same location and month.
(3) If you are an undisinfected system that begins using a disinfectant other than UV light after the dates in subpart U of this part for complying with the Initial Distribution System Evaluation requirements, you must consult with the State to identify compliance monitoring locations for this subpart. You must then develop a monitoring plan under § 141.622 that includes those monitoring locations.
Cite this article: FindLaw.com - Code of Federal Regulations Title 40. Protection of Environment § 40.141.621 Routine monitoring - last updated October 02, 2022 | https://codes.findlaw.com/cfr/title-40-protection-of-environment/cfr-sect-40-141-621/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature or via Westlaw before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw's Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)