If your system is a subpart H system serving fewer than 10,000 people and utilizing conventional filtration or direct filtration, you must conduct continuous monitoring of turbidity for each individual filter at your system. The following requirements apply to continuous turbidity monitoring:
(a) Monitoring must be conducted using an approved method in § 141.74(a);
(b) Calibration of turbidimeters must be conducted using procedures specified by the manufacturer;
(c) Results of turbidity monitoring must be recorded at least every 15 minutes;
(d) Monthly reporting must be completed according to § 141.570; and
(e) Records must be maintained according to § 141.571.
Cite this article: FindLaw.com - Code of Federal Regulations Title 40. Protection of Environment § 40.141.560 Is my system subject to individual filter turbidity requirements? - last updated January 02, 2025 | https://codes.findlaw.com/cfr/title-40-protection-of-environment/cfr-sect-40-141-560/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)