As stated in § 63.7520, you must comply with the following requirements for performance test for existing, new or reconstructed affected sources:
Table 5 to Subpart DDDDD of Part 63—Performance Testing Requirements |
||
---|---|---|
To conduct a performance test for the following pollutant . . . |
You must . . . |
Using, as appropriate . . . |
1. Filterable PM |
a. Select sampling ports location and the number of traverse points |
Method 1 at 40 CFR part 60, appendix A-1 of this chapter. |
b. Determine velocity and volumetric flow-rate of the stack gas |
Method 2, 2F, or 2G at 40 CFR part 60, appendix A-1 or A-2 to part 60 of this chapter. |
|
c. Determine oxygen or carbon dioxide concentration of the stack gas |
Method 3A or 3B at 40 CFR part 60, appendix A-2 to part 60 of this chapter, or ANSI/ASME PTC 19.10-1981.a |
|
d. Measure the moisture content of the stack gas |
Method 4 at 40 CFR part 60, appendix A-3 of this chapter. |
|
e. Measure the PM emission concentration |
Method 5 or 17 (positive pressure fabric filters must use Method 5D) at 40 CFR part 60, appendix A-3 or A-6 of this chapter. |
|
f. Convert emissions concentration to lb per MMBtu emission rates |
Method 19 F-factor methodology at 40 CFR part 60, appendix A-7 of this chapter. |
|
2. TSM |
a. Select sampling ports location and the number of traverse points |
Method 1 at 40 CFR part 60, appendix A-1 of this chapter. |
b. Determine velocity and volumetric flow-rate of the stack gas |
Method 2, 2F, or 2G at 40 CFR part 60, appendix A-1 or A-2 of this chapter. |
|
c. Determine oxygen or carbon dioxide concentration of the stack gas |
Method 3A or 3B at 40 CFR part 60, appendix A-1 of this chapter, or ANSI/ASME PTC 19.10-1981.a |
|
d. Measure the moisture content of the stack gas |
Method 4 at 40 CFR part 60, appendix A-3 of this chapter. |
|
e. Measure the TSM emission concentration |
Method 29 at 40 CFR part 60, appendix A-8 of this chapter |
|
f. Convert emissions concentration to lb per MMBtu emission rates |
Method 19 F-factor methodology at 40 CFR part 60, appendix A-7 of this chapter. |
|
3. Hydrogen chloride |
a. Select sampling ports location and the number of traverse points |
Method 1 at 40 CFR part 60, appendix A-1 of this chapter. |
b. Determine velocity and volumetric flow-rate of the stack gas |
Method 2, 2F, or 2G at 40 CFR part 60, appendix A-2 of this chapter. |
|
c. Determine oxygen or carbon dioxide concentration of the stack gas |
Method 3A or 3B at 40 CFR part 60, appendix A-2 of this chapter, or ANSI/ASME PTC 19.10-1981.a |
|
d. Measure the moisture content of the stack gas |
Method 4 at 40 CFR part 60, appendix A-3 of this chapter. |
|
e. Measure the hydrogen chloride emission concentration |
Method 26 or 26A (M26 or M26A) at 40 CFR part 60, appendix A-8 of this chapter. |
|
f. Convert emissions concentration to lb per MMBtu emission rates |
Method 19 F-factor methodology at 40 CFR part 60, appendix A-7 of this chapter. |
|
4. Mercury |
a. Select sampling ports location and the number of traverse points |
Method 1 at 40 CFR part 60, appendix A-1 of this chapter. |
b. Determine velocity and volumetric flow-rate of the stack gas |
Method 2, 2F, or 2G at 40 CFR part 60, appendix A-1 or A-2 of this chapter. |
|
c. Determine oxygen or carbon dioxide concentration of the stack gas |
Method 3A or 3B at 40 CFR part 60, appendix A-1 of this chapter, or ANSI/ASME PTC 19.10-1981.a |
|
d. Measure the moisture content of the stack gas |
Method 4 at 40 CFR part 60, appendix A-3 of this chapter. |
|
e. Measure the mercury emission concentration |
Method 29, 30A, or 30B (M29, M30A, or M30B) at 40 CFR part 60, appendix A-8 of this chapter or Method 101A at 40 CFR part 61, appendix B of this chapter, or ASTM Method D6784.a |
|
f. Convert emissions concentration to lb per MMBtu emission rates |
Method 19 F-factor methodology at 40 CFR part 60, appendix A-7 of this chapter. |
|
5. CO |
a. Select the sampling ports location and the number of traverse points |
Method 1 at 40 CFR part 60, appendix A-1 of this chapter. |
b. Determine oxygen concentration of the stack gas |
Method 3A or 3B at 40 CFR part 60, appendix A-3 of this chapter, or ASTM D6522-00 (Reapproved 2005), or ANSI/ASME PTC 19.10-1981.a |
|
c. Measure the moisture content of the stack gas |
Method 4 at 40 CFR part 60, appendix A-3 of this chapter. |
|
d. Measure the CO emission concentration |
Method 10 at 40 CFR part 60, appendix A-4 of this chapter. Use a measurement span value of 2 times the concentration of the applicable emission limit. |
a Incorporated by reference, see § 63.14.
Cite this article: FindLaw.com - Code of Federal Regulations Title 40. Protection of Environment 40 CFR Pt. 63, Subpt. DDDDD, Tbl. 5 TABLE 5 TO SUBPART DDDDD OF PART 63—PERFORMANCE TESTING REQUIREMENTS - last updated October 02, 2022 | https://codes.findlaw.com/cfr/title-40-protection-of-environment/cfr-pt-40-63-subpt-ddddd-tbl-5/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature or via Westlaw before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw's Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)