To measure the following pollutants |
Use the following methods in appendix A of this part to determine the sampling location |
Use the following methods in appendix A of this part to measure pollutant concentration |
Also note the following additional information |
|
|---|---|---|---|---|
|
1. Organics |
||||
|
Dioxins/Furans |
Method 1 |
Method 23 a |
The minimum sampling time must be 4 hours per test run while the municipal waste combustion unit is operating at full load. |
|
|
2. Metals |
||||
|
Cadmium |
Method 1 |
Method 29 a |
Compliance testing must be performed while the municipal waste combustion unit is operating at full load. |
|
|
Lead |
Method 1 |
Method 29 a |
Compliance testing must be performed while the municipal waste combustion unit is operating at full load. |
|
|
Mercury |
Method 1 |
Method 29 a |
Compliance testing must be performed while the municipal waste combustion unit is operating at full load. |
|
|
Opacity |
Method 9 |
Method 9 |
Use Method 9 to determine compliance with opacity limits. 3-hour observation period (thirty 6-minute averages). |
|
|
Particulate Matter |
Method 1 |
Method 5 or 29 |
The minimum sample volume must be 1.0 cubic meters. The probe and filter holder heating systems in the sample train must be set to provide a gas temperature no greater than 160 ±14 °C. The minimum sampling time is 1 hour. |
|
|
3. Acid Gases b |
||||
|
Hydrogen Chloride |
Method 1 |
Method 26 or 26A a |
Test runs must be at least 1 hour long while the municipal waste combustion unit is operating at full load. |
|
|
4. Other b |
||||
|
Fugitive Ash |
Not applicable |
Method 22 (visible emissions) |
The three 1-hour observation period must include periods when the facility transfers fugitive ash from the municipal waste combustion unit to the area where the fugitive ash is stored or loaded into containers or trucks. |
a Must simultaneously measure oxygen (or carbon dioxide) using Method 3A or 3B in appendix A of this part.
b Use CEMS to test sulfur dioxide, nitrogen oxide, and carbon monoxide. Stack tests are not required except for quality assurance requirements in appendix F of this part.
Cite this article: FindLaw.com - Code of Federal Regulations Title 40. Protection of Environment 40 CFR Pt. 60, Subpt. BBBB, Tbl. 8 Table 8 to Subpart BBBB of Part 60—Model Rule—Requirements for Stack Tests - last updated January 02, 2025 | https://codes.findlaw.com/cfr/title-40-protection-of-environment/cfr-pt-40-60-subpt-bbbb-tbl-8/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)