(a) Except as provided in paragraphs (c), (d), and (e) of this section, each facility to which this part applies must have fixed catchments, curbing, or other fixed means to contain oil or hazardous material discharged in at least—
(1) Each hose handling and loading arm area (that area on the facility that is within the area traversed by the free end of the hose or loading arm when moved from its normal stowed or idle position into a position for connection);
(2) Each hose connection manifold area; and
(3) Under each hose connection that will be coupled or uncoupled as part of the transfer operation during coupling, uncoupling, and transfer.
(b) The discharge containment means required by paragraph (a) of this section must have a capacity of at least:
(1) Two barrels if it serves one or more hoses of 6–inch inside diameter or smaller, or loading arms of 6–inch nominal pipe size diameter or smaller;
(2) Three barrels if it serves one or more hoses with an inside diameter of more than 6–inches, but less than 12 inches, or loading arms with a nominal pipe size diameter of more than 6 inches, but less than 12 inches; or
(3) Four barrels if it serves one or more hoses of 12–inch inside diameter or larger, or loading arms of 12–inch nominal pipe size diameter or larger.
(c) The facility may use portable means of not less than 1/2 barrel capacity each to meet the requirements of paragraph (a) of this section for part or all of the facility if the COTP finds that fixed means to contain oil or hazardous material discharges are not feasible.
(d) A mobile facility may have portable means of not less than five gallons capacity to meet the requirements of paragraph (a) of this section.
(e) Fixed or portable containment may be used to meet the requirements of paragraph (a)(3) of this section.
Cite this article: FindLaw.com - Code of Federal Regulations Title 33. Navigation and Navigable Waters § 33.154.530 Small discharge containment - last updated January 02, 2025 | https://codes.findlaw.com/cfr/title-33-navigation-and-navigable-waters/cfr-sect-33-154-530/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw’s Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)