Current as of October 02, 2022 | Updated by FindLaw Staff
(a) Approved portable and semi-portable extinguishers must be installed in accordance with Table 145.10(a).
(b) Semi-portable extinguishers must be located in the open so as to be readily seen.
(c) Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so all of the space can be protected.
(d) Table 145.10(a) of this section indicates the minimum number and size of fire extinguishers required for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.
Table 145.10(a)—Portable and Semi-Portable Extinguishers |
||
---|---|---|
Space |
Minimum required rating |
Quantity and location |
Safety Areas: |
||
Communicating corridors |
2-A |
1 in each main corridor not more than 150 ft apart. (May be located in stairways.) |
Radio room |
20-B:C |
1 in the vicinity of the exit. |
Accommodations: |
||
Sleeping accommodations |
2-A |
1 in each sleeping accommodation space outfitted for 4 or more persons. |
Service Spaces: |
||
Galleys |
40-B:C |
1 for each 2,500 sq ft of floor space or fraction thereof. |
Storerooms |
2-A |
1 for each 2,500 sq ft of floor space or fraction thereof. The extinguisher must be located in the vicinity of the exits, either inside or outside of spaces. |
Machinery Spaces: |
||
Gas-fired boilers |
40-B |
2 required. |
160-B |
1 required.1 |
|
Oil-fired boilers |
40-B |
2 required. |
160-B |
2 required.1 |
|
Internal combustion or gas turbine engines |
40-B |
1 for each engine.2 |
Electric motors or generators of open type |
40-B:C |
1 for each 2 motors or generators.3 |
1 Not required where a fixed extinguishing system is installed.
2 When the installation is on the weather deck or open to the atmosphere at all times, then one 40-B extinguisher for every three engines is allowable.
3 Small electrical appliances, such as fans, are exempt.
Cite this article: FindLaw.com - Code of Federal Regulations Title 33. Navigation and Navigable Waters § 33.145.10 Location, number, and installation of fire extinguishers - last updated October 02, 2022 | https://codes.findlaw.com/cfr/title-33-navigation-and-navigable-waters/cfr-sect-33-145-10/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature or via Westlaw before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw's Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)