(a) Low–Voltage Dry–Type Distribution Transformers.
(1) The efficiency of a low-voltage, dry-type distribution transformer manufactured on or after January 1, 2007, but before January 1, 2016, shall be no less than that required for the applicable kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase |
Three-phase |
||
---|---|---|---|
kVA |
% |
kVA |
% |
15 |
97.7 |
15 |
97.0 |
25 |
98.0 |
30 |
97.5 |
37.5 |
98.2 |
45 |
97.7 |
50 |
98.3 |
75 |
98.0 |
75 |
98.5 |
112.5 |
98.2 |
100 |
98.6 |
150 |
98.3 |
167 |
98.7 |
225 |
98.5 |
250 |
98.8 |
300 |
98.6 |
333 |
98.9 |
500 |
98.7 |
750 |
98.8 |
||
1000 |
98.9 |
||
Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431. |
(2) The efficiency of a low-voltage dry-type distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase |
Three-phase |
||
---|---|---|---|
kVA |
Efficiency |
kVA |
Efficiency |
(%) |
(%) |
||
15 |
97.70 |
15 |
97.89 |
25 |
98.00 |
30 |
98.23 |
37.5 |
98.20 |
45 |
98.40 |
50 |
98.30 |
75 |
98.60 |
75 |
98.50 |
112.5 |
98.74 |
100 |
98.60 |
150 |
98.83 |
167 |
98.70 |
225 |
98.94 |
250 |
98.80 |
300 |
99.02 |
333 |
98.90 |
500 |
99.14 |
750 |
99.23 |
||
1000 |
99.28 |
||
Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431. |
(b) Liquid–Immersed Distribution Transformers.
(1) The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase |
Three-phase |
||
---|---|---|---|
kVA |
Efficiency |
kVA |
Efficiency |
(%) |
(%) |
||
10 |
98.62 |
15 |
98.36 |
15 |
98.76 |
30 |
98.62 |
25 |
98.91 |
45 |
98.76 |
37.5 |
99.01 |
75 |
98.91 |
50 |
99.08 |
112.5 |
99.01 |
75 |
99.17 |
150 |
99.08 |
100 |
99.23 |
225 |
99.17 |
167 |
99.25 |
300 |
99.23 |
250 |
99.32 |
500 |
99.25 |
333 |
99.36 |
750 |
99.32 |
500 |
99.42 |
1000 |
99.36 |
667 |
99.46 |
1500 |
99.42 |
833 |
99.49 |
2000 |
99.46 |
2500 |
99.49 |
||
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test—Procedure, Appendix A to Subpart K of 10 CFR part 431. |
(2) The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase |
Three-phase |
||
---|---|---|---|
kVA |
Efficiency |
kVA |
Efficiency |
(%) |
(%) |
||
10 |
98.70 |
15 |
98.65 |
15 |
98.82 |
30 |
98.83 |
25 |
98.95 |
45 |
98.92 |
37.5 |
99.05 |
75 |
99.03 |
50 |
99.11 |
112.5 |
99.11 |
75 |
99.19 |
150 |
99.16 |
100 |
99.25 |
225 |
99.23 |
167 |
99.33 |
300 |
99.27 |
250 |
99.39 |
500 |
99.35 |
333 |
99.43 |
750 |
99.40 |
500 |
99.49 |
1000 |
99.43 |
667 |
99.52 |
1500 |
99.48 |
833 |
99.55 |
2000 |
99.51 |
2500 |
99.53 |
||
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431. |
(c) Medium–Voltage Dry–Type Distribution Transformers.
(1) The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase |
Three-phase |
||||||
---|---|---|---|---|---|---|---|
BIL * |
BIL |
||||||
kVA |
20−45 kV |
46−95 kV |
≥96 kV |
kVA |
20−45 kV |
46−95 kV |
≥96 kV |
Efficiency |
Efficiency |
Efficiency |
Efficiency |
Efficiency |
Efficiency |
||
(%) |
(%) |
(%) |
(%) |
(%) |
(%) |
||
15 |
98.10 |
97.86 |
15 |
97.50 |
97.18 |
||
25 |
98.33 |
98.12 |
30 |
97.90 |
97.63 |
||
37.5 |
98.49 |
98.30 |
45 |
98.10 |
97.86 |
||
50 |
98.60 |
98.42 |
75 |
98.33 |
98.12 |
||
75 |
98.73 |
98.57 |
98.53 |
112.5 |
98.49 |
98.30 |
|
100 |
98.82 |
98.67 |
98.63 |
150 |
98.60 |
98.42 |
|
167 |
98.96 |
98.83 |
98.80 |
225 |
98.73 |
98.57 |
98.53 |
250 |
99.07 |
98.95 |
98.91 |
300 |
98.82 |
98.67 |
98.63 |
333 |
99.14 |
99.03 |
98.99 |
500 |
98.96 |
98.83 |
98.80 |
500 |
99.22 |
99.12 |
99.09 |
750 |
99.07 |
98.95 |
98.91 |
667 |
99.27 |
99.18 |
99.15 |
1000 |
99.14 |
99.03 |
98.99 |
833 |
99.31 |
99.23 |
99.20 |
1500 |
99.22 |
99.12 |
99.09 |
2000 |
99.27 |
99.18 |
99.15 |
||||
2500 |
99.31 |
99.23 |
99.20 |
||||
* BIL means basic impulse insulation level. |
|||||||
Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431. |
(2) The efficiency of a medium- voltage dry-type distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase |
Three-phase |
||||||
---|---|---|---|---|---|---|---|
BIL * |
BIL |
||||||
kVA |
20−45 kV |
46−95 kV |
≥96 kV |
kVA |
20−45 kV |
46−95 kV |
≥96 kV |
Efficiency |
Efficiency |
Efficiency |
Efficiency |
Efficiency |
Efficiency |
||
(%) |
(%) |
(%) |
(%) |
(%) |
(%) |
||
15 |
98.10 |
97.86 |
15 |
97.50 |
97.18 |
||
25 |
98.33 |
98.12 |
30 |
97.90 |
97.63 |
||
37.5 |
98.49 |
98.30 |
45 |
98.10 |
97.86 |
||
50 |
98.60 |
98.42 |
75 |
98.33 |
98.13 |
||
75 |
98.73 |
98.57 |
98.53 |
112.5 |
98.52 |
98.36 |
|
100 |
98.82 |
98.67 |
98.63 |
150 |
98.65 |
98.51 |
|
167 |
98.96 |
98.83 |
98.80 |
225 |
98.82 |
98.69 |
98.57 |
250 |
99.07 |
98.95 |
98.91 |
300 |
98.93 |
98.81 |
98.69 |
333 |
99.14 |
99.03 |
98.99 |
500 |
99.09 |
98.99 |
98.89 |
500 |
99.22 |
99.12 |
99.09 |
750 |
99.21 |
99.12 |
99.02 |
667 |
99.27 |
99.18 |
99.15 |
1000 |
99.28 |
99.20 |
99.11 |
833 |
99.31 |
99.23 |
99.20 |
1500 |
99.37 |
99.30 |
99.21 |
2000 |
99.43 |
99.36 |
99.28 |
||||
2500 |
99.47 |
99.41 |
99.33 |
||||
* BIL means basic impulse insulation level. |
|||||||
Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431. |
(d) Mining Distribution Transformers. [Reserved]
Cite this article: FindLaw.com - Code of Federal Regulations Title 10. Energy § 10.431.196 Energy conservation standards and their effective dates - last updated October 02, 2022 | https://codes.findlaw.com/cfr/title-10-energy/cfr-sect-10-431-196/
FindLaw Codes may not reflect the most recent version of the law in your jurisdiction. Please verify the status of the code you are researching with the state legislature or via Westlaw before relying on it for your legal needs.
A free source of state and federal court opinions, state laws, and the United States Code. For more information about the legal concepts addressed by these cases and statutes, visit FindLaw's Learn About the Law.
Get help with your legal needs
FindLaw’s Learn About the Law features thousands of informational articles to help you understand your options. And if you’re ready to hire an attorney, find one in your area who can help.
Search our directory by legal issue
Enter information in one or both fields (Required)